Electrical Work Activity Hazard Analysis
Published:
Electrical work on USACE and Department of Defense construction projects demands an Activity Hazard Analysis (AHA) that addresses the unique lethality of electrical hazards under the EM 385-1-1 safety framework. Electrocution is consistently among OSHA's "Fatal Four" causes of death in construction, and electrical incidents on federal projects carry additional complexity due to aging infrastructure, non-standard military power systems, and the frequent requirement to perform work on or near energized circuits that cannot be de-energized without mission impact. The AHA must demonstrate that the contractor has systematically identified every electrical hazard, applied the hierarchy of controls, and reduced the Risk Assessment Code to an acceptable residual level before any electrical work begins.
EM 385-1-1 Section 11 governs electrical safety on USACE projects and incorporates requirements from OSHA 29 CFR 1926 Subpart K, NFPA 70 (National Electrical Code), and NFPA 70E (Standard for Electrical Safety in the Workplace). Section 11 requires that all electrical work be performed in a de-energized state unless the contractor can demonstrate that de-energization introduces greater hazards or is infeasible. When energized work is unavoidable, an Energized Electrical Work Permit (EEWP) must be completed, approved by the SSHO and the project manager, and attached to the AHA. The EEWP documents the justification for energized work, the shock and arc flash boundaries, the required PPE category, and the specific safe work practices that will be followed.
The electrical AHA on a DoD project must identify each Definable Feature of Work within the electrical scope — rough-in, panel installation, terminations, testing, and energization are each distinct DFOWs that may require separate AHAs. Each work step carries a RAC rating that reflects both the probability and severity of electrical contact, with initial ratings for uncontrolled electrical work routinely falling in the Catastrophic or Critical severity range. Arc flash incidents alone can produce temperatures exceeding 35,000 degrees Fahrenheit and blast pressures sufficient to throw workers across a room, making the consequence analysis straightforward: any failure of controls can be fatal. The AHA is the contractor's primary tool for proving that these risks have been systematically addressed.
Disclaimer
This content is provided for general informational and educational purposes only. It is not a substitute for a site-specific Job Safety Analysis conducted by a qualified safety professional familiar with your workplace conditions, equipment, and personnel. OSHA citations, BLS statistics, and hazard controls referenced here may not reflect the most current standards or apply to your specific situation. Always consult current OSHA regulations, manufacturer guidelines, and a competent person before beginning work. Health & Safety Systems LLC assumes no liability for actions taken based on this content.
Definable Feature of Work (DFOW)
Electrical Installation & Maintenance
Covers all phases of electrical construction including conduit installation, wire pulling, device and panel installation, terminations, testing, and energization. Includes both new construction and renovation of existing electrical systems on federal facilities.
Typical Duration: 2-12 weeks
EM 385-1-1 References
Section 11.A: General Electrical Requirements
Establishes that all electrical work must be performed in a de-energized state unless infeasible, requires qualified electrical workers, and mandates lockout/tagout procedures for all circuits being worked on.
Section 11.B: Lockout/Tagout
Requires a written lockout/tagout program, individual locks for each worker, verification of zero-energy state, and procedures for complex lockout involving multiple energy sources.
Section 11.C: Assured Equipment Grounding Conductor Program
Requires either an assured grounding program or GFCI protection for all temporary power on construction sites, with documented testing at specified intervals.
Section 11.D: Working On or Near Energized Parts
Establishes approach boundaries, requires Energized Electrical Work Permits, specifies PPE requirements based on incident energy calculations, and prohibits energized work unless de-energization is infeasible or creates greater hazard.
Section 01.A.13: Activity Hazard Analysis Requirements
Defines the AHA format, content requirements, review process, and the requirement that AHAs be accepted before work begins on each DFOW.
Build This AHA in Minutes
Use JSABuilder to create, manage, and share professional Activity Hazard Analysis worksheets with your team.
Start Free TrialRisk Assessment Code (RAC)
The RAC matrix combines hazard severity and probability to assign a risk level before and after controls are applied. This AHA demonstrates risk reduction from initial to residual conditions.
Initial Risk (Before Controls)
High (2)
Severity: Catastrophic | Probability: Occasional
Residual Risk (After Controls)
Low (5)
Severity: Marginal | Probability: Unlikely
Step-by-Step AHA Breakdown
Step 1: Review AHA and Energized Electrical Work Permit with crew
Hazards
- Incomplete hazard communication
- Workers unaware of circuit voltages and configurations
- Failure to identify all energy sources
Controls
- Conduct pre-task safety briefing covering AHA, EEWP if applicable, and emergency procedures
- Review single-line diagrams and panel schedules for the work area
- Verify all crew members are qualified electrical workers per NFPA 70E
Step 2: Identify and verify energy sources
Hazards
- Unknown or undocumented circuits
- Multiple energy sources from different panels or buildings
- Back-fed circuits from generators or UPS systems
Controls
- Trace all circuits to their sources using single-line diagrams and field verification
- Identify back-feed potential from standby generators, UPS systems, and photovoltaic arrays
- Use non-contact voltage testers as initial screening, followed by contact-type meters for confirmation
Step 3: Perform lockout/tagout
Hazards
- Accidental re-energization
- Incomplete isolation of all energy sources
- Stored energy discharge (capacitors, UPS batteries)
Controls
- Apply individual lock and tag at each disconnect point
- Verify zero-energy state using rated voltage tester on all phases and neutral
- Test voltage tester on known live source before and after verification (live-dead-live method)
- Discharge capacitors and isolate battery systems before work
Step 4: Install conduit, raceways, and boxes
Hazards
- Electrical contact with existing live circuits in walls or ceilings
- Falls from ladders or scaffolds
- Struck by falling conduit or fittings
- Ergonomic strain from overhead work
Controls
- Scan walls and ceilings for existing live conductors before drilling or cutting
- Use appropriate fall protection for work above 6 feet
- Secure conduit and materials to prevent falling
- Rotate workers on overhead tasks to reduce fatigue
Step 5: Pull wire and cable
Hazards
- Electrical contact if pulling into energized panel or junction box
- Pinch points at conduit entries and pull boxes
- Ergonomic strain from manual pulling
- Cable insulation damage from excessive pulling tension
Controls
- Verify de-energized state of destination panel or box before pulling
- Use cable lubricant and properly sized pulling equipment to stay within cable tension limits
- Station workers at pull points to guide cable and prevent binding
- Inspect insulation for damage after pull is complete
Step 6: Make terminations and connections
Hazards
- Electrical shock from improperly isolated circuits
- Arc flash from accidental contact with energized bus or adjacent circuits
- Improper torque causing loose connections and future arc fault
Controls
- Re-verify zero-energy state immediately before opening panels or equipment
- Use insulated tools rated for the voltage class
- Torque all connections to manufacturer specifications using calibrated torque wrench
- Install barriers around adjacent energized equipment
Step 7: Install grounding and bonding
Hazards
- Shock from incomplete grounding system
- Improper ground path creating shock hazard on equipment enclosures
Controls
- Install grounding per NEC Article 250 and project specifications
- Verify ground continuity with megohmmeter
- Bond all metallic raceways, boxes, and equipment enclosures
- Test ground electrode resistance to verify adequate earth ground
Step 8: Test circuits and verify polarity
Hazards
- Shock during testing of energized circuits
- Arc flash when operating breakers or disconnects
- Incorrect wiring creating shock or fire hazard
Controls
- Wear voltage-rated PPE appropriate for the circuit voltage during testing
- Use properly rated test instruments with current calibration
- Verify correct phase rotation, polarity, and ground fault impedance
- Perform insulation resistance (megger) testing before energization
Step 9: Energize circuits
Hazards
- Arc flash during initial energization
- Equipment failure due to manufacturing defect or installation error
- Shock to personnel in the work area unaware of energization
Controls
- Clear all personnel from arc flash boundary before closing breakers
- Wear arc-rated PPE appropriate for the calculated incident energy level
- Stand to the side of panel or switchgear when closing breakers (never directly in front)
- Announce energization to all personnel in the area and verify area is clear
Step 10: Label panels and install arc flash warning signs
Hazards
- Future workers exposed to unlabeled electrical hazards
- Incorrect labeling causing improper PPE selection
Controls
- Label all panels, disconnects, and switchgear with circuit identification per NEC 408.4
- Install arc flash warning labels per NFPA 70E with incident energy level and required PPE category
- Provide as-built drawings to the facility reflecting all circuit changes
Competent & Qualified Persons
EM 385-1-1 requires designated competent and qualified persons for specific activities. These individuals must have the training, experience, and authority to identify hazards and take corrective action.
Qualified Electrical Worker
Must demonstrate skills and knowledge of electrical construction and the hazards involved through training and experience. Must be able to identify exposed live parts, determine nominal voltages, and know the approach distances specified in NFPA 70E Table 130.4(E)(a). Must hold current certification in CPR and AED use.
EM 385-1-1 Reference: Section EM 385-1-1 Section 11.A.02
Site Safety and Health Officer (SSHO)
Must hold 30-hour OSHA Construction certification, have minimum 5 years construction safety experience, complete EM 385-1-1 40-hour training, and be designated in the Accident Prevention Plan. Reviews and approves Energized Electrical Work Permits.
EM 385-1-1 Reference: Section EM 385-1-1 Section 01.A.17
Lockout/Tagout Authorized Person
Trained in lockout/tagout procedures, energy source identification, verification testing, and the specific lockout sequence for the equipment being serviced. Must understand the distinction between authorized, affected, and other employees.
EM 385-1-1 Reference: Section EM 385-1-1 Section 11.B
Quality Control Manager
Reviews AHAs for completeness and technical accuracy, ensures competent persons are designated by name, and coordinates AHA acceptance with the government representative before the electrical DFOW begins.
EM 385-1-1 Reference: Section EM 385-1-1 Section 01.A.13
Equipment, Training & Inspection Requirements
Required Equipment
Training Requirements
- NFPA 70E Electrical Safety qualified worker training including arc flash hazard awareness, approach boundaries, and PPE selection
- OSHA 10-hour Construction Safety (minimum for all workers; 30-hour for supervisors)
- EM 385-1-1 40-hour training for SSHO and qualified electrical persons
- Lockout/tagout authorized person training specific to the facility's electrical systems
- CPR/AED/First Aid certification (current) for all workers performing electrical tasks
Inspection Requirements
- Pre-use inspection of all insulated tools, rubber gloves, and voltage-rated PPE for cuts, holes, or damage before each use
- Verify voltage tester functionality on known live source before and after each use (live-dead-live protocol)
- Periodic testing of rubber insulating gloves per ASTM D120 schedule (Class 00 and 0 every 6 months, Class 1-4 every 6 months)
- Daily inspection of temporary power cords, GFCIs, and extension cords per assured grounding program
- SSHO documented weekly inspection of all electrical safety controls and PPE condition
Applicable OSHA Standards
29 CFR 1926.405
Wiring Methods, Components, and Equipment
Covers wiring design and protection, wiring methods for temporary and permanent installations, and requirements for cabinets, boxes, and fittings on construction sites.
29 CFR 1926.416
Safety-Related Work Practices
Prohibits work on energized circuits unless the employee can demonstrate the circuit is de-energized and grounded, or that energized work is essential and appropriate safety measures are in place.
29 CFR 1926.417
Lockout and Tagging of Circuits
Requires that circuits be de-energized and locked/tagged before work begins. Tags alone are not sufficient — locks must be used unless the employer can demonstrate that tagging provides equivalent protection.
29 CFR 1926.431
Maintenance of Equipment
Requires that electrical equipment be maintained in a safe condition and that only qualified persons perform maintenance on electrical equipment.
29 CFR 1926.432
Environmental Deterioration of Equipment
Requires that electrical equipment be suitable for the environment in which it is installed, including wet, damp, corrosive, and hazardous (classified) locations.
Required Personal Protective Equipment
Frequently Asked Questions
When is an Energized Electrical Work Permit required on a USACE project?
An Energized Electrical Work Permit (EEWP) is required under EM 385-1-1 Section 11.D whenever electrical work must be performed on circuits that cannot be de-energized. The permit must document the justification for energized work, the specific circuits involved, the calculated incident energy and arc flash boundary, the required PPE category, the qualified workers performing the task, and approval signatures from the SSHO and project manager. The EEWP is attached to the AHA and must be accepted by the government representative. Routine tasks such as voltage testing, thermographic scanning, and normal circuit breaker operation do not require an EEWP.
What is the difference between a qualified and unqualified electrical worker under EM 385?
A qualified electrical worker has been trained in and demonstrated skills and knowledge relevant to the construction and operation of electrical equipment and installations, and the hazards involved. They can identify exposed energized parts, know the approach distances per NFPA 70E, and are permitted to work within the limited approach boundary. An unqualified worker has not received this training and must stay outside the limited approach boundary at all times. On USACE projects, only qualified electrical workers may perform electrical construction, maintenance, or testing tasks.
How does the AHA address arc flash hazards?
The AHA must identify arc flash as a hazard for any work step that involves operating, opening, or working near energized electrical equipment. The controls section must specify the calculated incident energy level (in cal/cm2) at the working distance, the corresponding PPE category per NFPA 70E Table 130.7(C)(15)(a), the arc flash boundary distance, and the specific PPE required. If an arc flash study has not been completed for the facility, the AHA must use the NFPA 70E table method to determine PPE requirements based on equipment type and available fault current.
What RAC ratings are typical for electrical work steps?
Initial (pre-control) RAC ratings for electrical work steps typically range from Extremely High (1) to High (2) for tasks involving potential contact with energized circuits, since the severity of electrocution or arc flash is Catastrophic. After applying controls — de-energization, lockout/tagout, verification testing, insulated tools, and arc-rated PPE — the residual RAC should be reduced to Medium (3) or Low (4-5). Any work step with a residual RAC of High (2) or above requires additional controls or management review before the work can proceed.
What additional requirements does EM 385-1-1 impose beyond OSHA for electrical work?
EM 385-1-1 imposes several requirements beyond OSHA's Subpart K. These include mandatory GFCI protection on all temporary 120V 15- and 20-amp circuits (OSHA allows an assured grounding program as an alternative), requirement for an SSHO with 40-hour EM 385 training on site during all electrical work, formal AHA submission and acceptance before the DFOW begins, written Energized Electrical Work Permits that must be approved at the project management level, and the RAC matrix risk assessment for every work step. The EM 385 standard is generally more prescriptive and documentation-intensive than OSHA general industry or construction electrical standards.